https://ttsui.futurismdemo.com/Media/Images/500X644//Otis Instruments_41035.png

Omniguard Model 860 Flame Detector

The Omniguard Model 860 UV/IR flame detector is designed to detect unwanted fires and output alarm information. The Model 860 senses ultraviolet radiation and infrared radiation in the appropriate wavelengths for early fire detection. Utilizes the patented Fire Event Analysis Algorithm to provide superior false alarm immunity. Available in two versions: one is for hydrocarbon fires only, and one is for hydrocarbon and certain non-hydrocarbon fires.

Availability: In stock
Request A Quote

Specification

Omniguard Model 860 Flame Detector

Optional Accessories

- Swivel Mount: No. 20856 (Used with Aluminum), No. 70991 (Used with Stainless Steel)

- Portable Test Unit: Model 540 / 545

- Air Shield Assy Kit: No. 8001023

- Rain Shield: No. 23546

Operating Temperature Range

-40°F to 185ºF (-40°C to 85°C)

Spectral Response

UV: Peak Sensitivities of 0.22 pm; Infrared: Peak of 4.4 pm (Standard), and 2.9 pm and 4.4 pm (Dual Pass)

Certifications & Approvals

- Class I, Division 1, Groups B. C & D (Explosion Proof)

- Class II, Division 1, Groups E, F & G (Dust Ignition Proof)

- NEMA 4X Weatherproof, Dust-Tight, Watertight

- CE0081 Ex d II 2 G/D

- Ex d IIB+H2 T5 Gb for Gas on 660-0X000

- Ex tb IIIC T100°C Db IP6X for Dust on 660-0X000x

- Ex d IIB+H2 T4 Gb for Gas on 660-1X000

- Ex tb IIIC T1 135°C Db IP6X for Dust on 660-12000

- Copper-free Aluminum Housing Conversion Coated to MIL-C-5541C. Class 3 (White) - Standard

- Stainless Steel Housing with Passive Finish per MIL-5-5002C, Type 1 - Optional

Output

- Relay

Relays (2): Fire, Trouble, Dry Contacts, Hermetically Sealed

Rated: 2 A at 28 VDC (User Selects NO or NC)

Fire Relay: User Selects Latching or Non-Latching

- Current Loop (Standard Version): 0 to 20 mA Output

20 mA = Fire

16 mA = UV or IR Presence

4 mA = Ready

0 mA = 20

Nominal Voltage

24 VDC (Ripple Voltage <240mV)

Voltage Range

20 to 30 VDC

Power Consumption

90 mA (Standby), 110 mA (Alarm), 250 mA (Auto and Manual Test)

Digital Output

Programmable RS-485 Modbus Serial Output

Dimensions

4.5 H x 5.5 W x 6 D in.

Total Weight

5 lbs. (Aluminum), 13 lbs. (Stainless Steel)

Conduit Entry

3/4-14 NPTF or M20-1.5